Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Degree of protection (IP)IP30
Rated voltage600 - 600V
Overload release current setting480.0 - 1200A
Position of connection for main current circuitBack side
Rated permanent current Iu1200A
Number of poles3
Adjustment range short-term delayed short-circuit release720.0 - 12000A
Type of electrical connection of main circuitBolt connection
Type of control elementPush button
Motor drive integratedNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
With switched-off indicatorYes
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release1800.0 - 18000A
With under voltage releaseNo
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA076942R1 | E1.2N-A 1200 Ekip Touch LSI 3p F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally closed contact

0

Degree of protection (IP)

IP30

Rated voltage

600 .. 600V

Overload release current setting

480.0 .. 1200A

Position of connection for main current circuit

Back side

Rated permanent current Iu

1200A

Number of poles

3

Adjustment range short-term delayed short-circuit release

720.0 .. 12000A

Type of electrical connection of main circuit

Bolt connection

Type of control element

Push button

Motor drive integrated

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

With switched-off indicator

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

1800.0 .. 18000A

With under voltage release

Motor drive optional

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.