Technical specifications

Overload release current setting480 - 1200A
Type of control elementPush button
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP30
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitBack side
Adjustment range undelayed short-circuit release1800 - 18000A
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release720 - 12000A
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionYes
Complete device with protection unitYes
Device constructionBuilt-in device fixed built-in technique
Rated permanent current Iu1200A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA