Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Rated permanent current Iu400A
Number of poles3
Overload release current setting160.0 - 400A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Rated voltage600 - 600V
Motor drive integratedNo
DIN rail (top hat rail) mounting optionalNo
With under voltage releaseNo
Integrated earth fault protectionYes
Adjustment range undelayed short-circuit release600.0 - 6000A
Type of control elementPush button
Adjustment range short-term delayed short-circuit release240.0 - 4000A
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
Position of connection for main current circuitBack side
Complete device with protection unitYes
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Type of electrical connection of main circuitBolt connection
Motor drive optionalYes
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA076960R1 | E1.2S-A 400 Ekip Dip LSIG 3p F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

400A

Number of poles

3

Overload release current setting

160.0 .. 400A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Rated voltage

600 .. 600V

Motor drive integrated

DIN rail (top hat rail) mounting optional

With under voltage release

Integrated earth fault protection

Adjustment range undelayed short-circuit release

600.0 .. 6000A

Type of control element

Push button

Adjustment range short-term delayed short-circuit release

240.0 .. 4000A

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device fixed built-in technique

Position of connection for main current circuit

Back side

Complete device with protection unit

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Type of electrical connection of main circuit

Bolt connection

Motor drive optional

Degree of protection (IP)

IP30

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.