Number of auxiliary contacts as normally open contact0
Overload release current setting320.0 - 800A
Rated permanent current Iu800 A
With integrated under voltage releaseNo
Number of poles3
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Rated voltage600 - 600V
Degree of protection (IP)IP30
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Type of electrical connection of main circuitBolt connection
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Device constructionBuilt-in device fixed built-in technique
Motor drive integratedNo
Type of control elementPush button
Motor drive optionalYes
Position of connection for main current circuitBack side
With switched-off indicatorYes
Adjustment range undelayed short-circuit release1200.0 - 12000A
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA076972R1 | E1.2S-A 800 Ekip Touch LSI 3p F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Overload release current setting

320.0 .. 800A

Rated permanent current Iu

800 A

With integrated under voltage release

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally closed contact

0

Rated voltage

600 .. 600V

Degree of protection (IP)

IP30

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Type of electrical connection of main circuit

Bolt connection

Suitable for DIN rail (top hat rail) mounting

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Device construction

Built-in device fixed built-in technique

Motor drive integrated

Type of control element

Push button

Motor drive optional

Position of connection for main current circuit

Back side

With switched-off indicator

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.