Technical specifications

Overload release current setting320.0 - 800A
Degree of protection (IP)IP30
Position of connection for main current circuitBack side
Number of auxiliary contacts as normally closed contact0
Type of control elementPush button
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Motor drive integratedNo
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Type of electrical connection of main circuitBolt connection
With switched-off indicatorYes
Motor drive optionalYes
Integrated earth fault protectionNo
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release1200.0 - 12000A
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
With under voltage releaseNo
Device constructionBuilt-in device fixed built-in technique
Rated permanent current Iu800A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA076992R1 | E1.2B-A 800 Ekip Touch LSI 4p F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting

320.0 .. 800A

Degree of protection (IP)

IP30

Position of connection for main current circuit

Back side

Number of auxiliary contacts as normally closed contact

0

Type of control element

Push button

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Motor drive integrated

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Type of electrical connection of main circuit

Bolt connection

With switched-off indicator

Motor drive optional

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

DIN rail (top hat rail) mounting optional

Complete device with protection unit

With under voltage release

Device construction

Built-in device fixed built-in technique

Rated permanent current Iu

800A

Number of poles

4

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA