Technical specifications
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Overload release current setting
480.0 .. 1200A
Type of control element
Push button
With under voltage release
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
720.0 .. 12000A
Adjustment range undelayed short-circuit release
1800.0 .. 18000A
Motor drive integrated
With switched-off indicator
Position of connection for main current circuit
Back side
Motor drive optional
Complete device with protection unit
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
1200A
Number of poles
4
Rated voltage
600 .. 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA