  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu800 A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Number of poles4
Rated voltage600 - 600V
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
With integrated under voltage releaseNo
Position of connection for main current circuitBack side
Type of control elementPush button
Overload release current setting320.0 - 800A
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
Adjustment range undelayed short-circuit release1200.0 - 12000A
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Complete device with protection unitYes
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release480.0 - 8000A
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077009R1 | E1.2N-A 800 Ekip Dip LSI 4p F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

800 A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of poles

4

Rated voltage

600 .. 600V

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

With integrated under voltage release

Position of connection for main current circuit

Back side

Type of control element

Push button

Overload release current setting

320.0 .. 800A

Motor drive optional

Device construction

Built-in device fixed built-in technique

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Suitable for DIN rail (top hat rail) mounting

With switched-off indicator

DIN rail (top hat rail) mounting optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Complete device with protection unit

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.