Technical specifications

Overload release current setting480 - 1200A
Number of auxiliary contacts as normally open contact0
Motor drive integratedNo
Degree of protection (IP)IP30
Position of connection for main current circuitBack side
With integrated under voltage releaseNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Adjustment range undelayed short-circuit release1800 - 18000A
Type of electrical connection of main circuitBolt connection
Adjustment range short-term delayed short-circuit release720 - 12000A
Suitable for DIN rail (top hat rail) mountingNo
Type of control elementPush button
With switched-off indicatorYes
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Motor drive optionalYes
Integrated earth fault protectionYes
Rated permanent current Iu1200A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA