Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting320 - 800A
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitConnection at separate chassis part
With integrated under voltage releaseNo
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Number of auxiliary contacts as change-over contact4
DIN rail (top hat rail) mounting optionalNo
With switched-off indicatorYes
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release- - -A
Integrated earth fault protectionNo
Motor drive optionalYes
Adjustment range undelayed short-circuit release1200 - 12000A
Type of control elementPush button
Suitable for DIN rail (top hat rail) mountingNo
Rated permanent current Iu800A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user