Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
Degree of protection (IP)
IP30
Rated permanent current Iu
1200A
Position of connection for main current circuit
Connection at separate chassis part
Overload release current setting
480.0 .. 1200A
Rated voltage
600 .. 600V
Type of control element
Push button
Adjustment range undelayed short-circuit release
1800.0 .. 18000A
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
720.0 .. 12000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
With switched-off indicator
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Motor drive optional
With under voltage release
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit