Technical specifications

Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu1200A
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitConnection at separate chassis part
Rated voltage600 - 600V
Type of control elementPush button
With switched-off indicatorYes
Position of connection for main current circuitConnection at separate chassis part
Number of poles3
Degree of protection (IP)IP30
Integrated earth fault protectionNo
Motor drive optionalYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Overload release current setting480.0 - 1200A
Adjustment range short-term delayed short-circuit release720.0 - 12000A
Motor drive integratedNo
Number of auxiliary contacts as change-over contact4
Adjustment range undelayed short-circuit release1800.0 - 18000A
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077142R1 | E1.2S-A 1200 Ekip Touch LSI 3p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

1200A

Number of auxiliary contacts as normally open contact

0

Type of electrical connection of main circuit

Connection at separate chassis part

Rated voltage

600 .. 600V

Type of control element

Push button

With switched-off indicator

Position of connection for main current circuit

Connection at separate chassis part

Number of poles

3

Degree of protection (IP)

IP30

Integrated earth fault protection

Motor drive optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Overload release current setting

480.0 .. 1200A

Adjustment range short-term delayed short-circuit release

720.0 .. 12000A

Motor drive integrated

Number of auxiliary contacts as change-over contact

4

Adjustment range undelayed short-circuit release

1800.0 .. 18000A

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device slide-in technique (withdrawable)

With under voltage release

DIN rail (top hat rail) mounting optional

Complete device with protection unit