Aleta.hr
Announcement

Registration is currently available to business customers only (B2B).

Details

  • •ZRACNI PREKIDAC EMAX2
  • •Low-voltage industrial components
  • •Power circuit-breaker for trafo/generator/installation protection
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Overload release current setting480 - 1200A
Number of auxiliary contacts as change-over contact4
Type of electrical connection of main circuitConnection at separate chassis part
Motor drive integratedNo
Position of connection for main current circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release1800 - 18000A
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionYes
Type of control elementPush button
Adjustment range short-term delayed short-circuit release720 - 12000A
Motor drive optionalYes
Degree of protection (IP)IP30
Suitable for DIN rail (top hat rail) mountingNo
Complete device with protection unitYes
Rated permanent current Iu1200A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as