Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Overload release current setting320.0 - 800A
Position of connection for main current circuitConnection at separate chassis part
Motor drive optionalYes
Integrated earth fault protectionYes
Suitable for DIN rail (top hat rail) mountingNo
With under voltage releaseNo
Type of control elementPush button
Complete device with protection unitYes
Type of electrical connection of main circuitConnection at separate chassis part
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Adjustment range undelayed short-circuit release1200.0 - 12000A
With switched-off indicatorYes
Motor drive integratedNo
Rated permanent current Iu800A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077156R1 | E1.2B-A 800 Ekip Hi-Touch LSIG 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP30

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally closed contact

0

Overload release current setting

320.0 .. 800A

Position of connection for main current circuit

Connection at separate chassis part

Motor drive optional

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Type of control element

Push button

Complete device with protection unit

Type of electrical connection of main circuit

Connection at separate chassis part

DIN rail (top hat rail) mounting optional

Device construction

Built-in device slide-in technique (withdrawable)

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

With switched-off indicator

Motor drive integrated

Rated permanent current Iu

800A

Number of poles

4

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.