Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
Overload release current setting320 - 800A
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Number of auxiliary contacts as normally closed contact0
Degree of protection (IP)IP30
Type of control elementPush button
DIN rail (top hat rail) mounting optionalNo
Type of electrical connection of main circuitConnection at separate chassis part
Motor drive optionalYes
Integrated earth fault protectionYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
With under voltage releaseNo
Adjustment range short-term delayed short-circuit release480 - 8000A
With switched-off indicatorYes
Adjustment range undelayed short-circuit release1200 - 12000A
Complete device with protection unitYes
Rated permanent current Iu800A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user