Position of connection for main current circuitConnection at separate chassis part
Number of auxiliary contacts as normally open contact0
Adjustment range undelayed short-circuit release1200 - 12000A
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Type of control elementPush button
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorYes
Number of auxiliary contacts as normally closed contact0
Integrated earth fault protectionYes
Overload release current setting320 - 800A
Adjustment range short-term delayed short-circuit release480 - 8000A
Type of electrical connection of main circuitConnection at separate chassis part
Complete device with protection unitYes
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated permanent current Iu800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA