Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Type of electrical connection of main circuitConnection at separate chassis part
Position of connection for main current circuitConnection at separate chassis part
Type of control elementPush button
Degree of protection (IP)IP30
Motor drive integratedNo
Overload release current setting160.0 - 400A
With under voltage releaseNo
Adjustment range undelayed short-circuit release600.0 - 6000A
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release240.0 - 4000A
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionYes
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated permanent current Iu400A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077206R1 | E1.2S-A 400 Ekip Hi-Touch LSIG 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Type of electrical connection of main circuit

Connection at separate chassis part

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Degree of protection (IP)

IP30

Motor drive integrated

Overload release current setting

160.0 .. 400A

With under voltage release

Adjustment range undelayed short-circuit release

600.0 .. 6000A

With switched-off indicator

Adjustment range short-term delayed short-circuit release

240.0 .. 4000A

Complete device with protection unit

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Motor drive optional

Device construction

Built-in device slide-in technique (withdrawable)

Rated permanent current Iu

400A

Number of poles

4

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA