Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Type of electrical connection of main circuitConnection at separate chassis part
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Overload release current setting160.0 - 400A
Motor drive integratedNo
Number of auxiliary contacts as change-over contact4
Device constructionBuilt-in device slide-in technique (withdrawable)
With switched-off indicatorYes
Integrated earth fault protectionYes
Suitable for DIN rail (top hat rail) mountingNo
Type of control elementPush button
Adjustment range short-term delayed short-circuit release240.0 - 4000A
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release600.0 - 6000A
Motor drive optionalYes
Complete device with protection unitYes
Rated permanent current Iu400 A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077207R1 | E1.2S-A 400 Ekip G Hi-Touch LSIG 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

With integrated under voltage release

Type of electrical connection of main circuit

Connection at separate chassis part

Position of connection for main current circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Overload release current setting

160.0 .. 400A

Motor drive integrated

Number of auxiliary contacts as change-over contact

4

Device construction

Built-in device slide-in technique (withdrawable)

With switched-off indicator

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Type of control element

Push button

Adjustment range short-term delayed short-circuit release

240.0 .. 4000A

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

600.0 .. 6000A

Motor drive optional

Complete device with protection unit

Rated permanent current Iu

400 A

Number of poles

4

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA