Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA077207R1 | E1.2S-A 400 Ekip G Hi-Touch LSIG 4p WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
With integrated under voltage release
Type of electrical connection of main circuit
Connection at separate chassis part
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Overload release current setting
160.0 .. 400A
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device slide-in technique (withdrawable)
With switched-off indicator
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Adjustment range short-term delayed short-circuit release
240.0 .. 4000A
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
600.0 .. 6000A
Motor drive optional
Complete device with protection unit
Rated permanent current Iu
400 A
Number of poles
4
Rated voltage
600 .. 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA