Technical specifications

Number of auxiliary contacts as normally open contact0
Overload release current setting320 - 800A
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
Type of electrical connection of main circuitConnection at separate chassis part
With switched-off indicatorYes
Motor drive integratedNo
Type of control elementPush button
Adjustment range short-term delayed short-circuit release480 - 8000A
Adjustment range undelayed short-circuit release1200 - 12000A
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionYes
Complete device with protection unitYes
Rated permanent current Iu800A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA