Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)IP30
Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitConnection at separate chassis part
Overload release current setting480 - 1200A
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitConnection at separate chassis part
Motor drive integratedNo
Type of control elementPush button
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release- - -A
Adjustment range undelayed short-circuit release1800 - 18000A
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Complete device with protection unitYes
Motor drive optionalYes
Rated permanent current Iu1200A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA