Technical specifications

With integrated under voltage releaseNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP30
Overload release current setting640.0 - 1600A
Number of auxiliary contacts as change-over contact4
Position of connection for main current circuitBack side
Adjustment range undelayed short-circuit release2400.0 - 24000A
Suitable for DIN rail (top hat rail) mountingNo
Motor drive integratedNo
Type of control elementPush button
Adjustment range short-term delayed short-circuit release- - -A
With switched-off indicatorYes
Type of electrical connection of main circuitBolt connection
Integrated earth fault protectionNo
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Device constructionBuilt-in device fixed built-in technique
Rated permanent current Iu1600A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077231R1 | E2.2B-A 1600 Ekip Touch LI 3p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP30

Overload release current setting

640.0 .. 1600A

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Back side

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Suitable for DIN rail (top hat rail) mounting

Motor drive integrated

Type of control element

Push button

Adjustment range short-term delayed short-circuit release

- .. -A

With switched-off indicator

Type of electrical connection of main circuit

Bolt connection

Integrated earth fault protection

Motor drive optional

DIN rail (top hat rail) mounting optional

Complete device with protection unit

Device construction

Built-in device fixed built-in technique

Rated permanent current Iu

1600A

Number of poles

3

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA