Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Device constructionBuilt-in device fixed built-in technique
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Degree of protection (IP)IP30
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorYes
Adjustment range undelayed short-circuit release3000.0 - 30000A
With under voltage releaseNo
Integrated earth fault protectionYes
Adjustment range short-term delayed short-circuit release1200.0 - 20000A
Overload release current setting800.0 - 2000A
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Type of control elementPush button
Position of connection for main current circuitBack side
Rated permanent current Iu2000A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077274R1 | E2.2H-A 2000 Ekip G Touch LSIG 3p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Device construction

Built-in device fixed built-in technique

Complete device with protection unit

DIN rail (top hat rail) mounting optional

Motor drive optional

Degree of protection (IP)

IP30

Suitable for DIN rail (top hat rail) mounting

With switched-off indicator

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

With under voltage release

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

1200.0 .. 20000A

Overload release current setting

800.0 .. 2000A

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

Type of control element

Push button

Position of connection for main current circuit

Back side

Rated permanent current Iu

2000A

Number of poles

3

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.