Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA077292R1 | E2.2N-A 2000 Ekip Touch LSI 3p F HR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
2000A
With integrated under voltage release
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
800.0 .. 2000A
Suitable for DIN rail (top hat rail) mounting
Rated voltage
600 .. 600V
Type of control element
Push button
Position of connection for main current circuit
Back side
Motor drive integrated
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Degree of protection (IP)
IP30
With switched-off indicator
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Motor drive optional
Integrated earth fault protection
Complete device with protection unit