Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu800 A
Degree of protection (IP)IP30
Position of connection for main current circuitBack side
With integrated under voltage releaseNo
Overload release current setting320.0 - 800A
Number of poles3
Rated voltage600 - 600V
Type of electrical connection of main circuitBolt connection
DIN rail (top hat rail) mounting optionalNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Type of control elementPush button
Device constructionBuilt-in device fixed built-in technique
Motor drive integratedNo
Adjustment range undelayed short-circuit release1200.0 - 12000A
With switched-off indicatorYes
Integrated earth fault protectionNo
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Complete device with protection unitYes
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Number of auxiliary contacts as change-over contact4
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077302R1 | E2.2S-A 800 Ekip Touch LSI 3p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

800 A

Degree of protection (IP)

IP30

Position of connection for main current circuit

Back side

With integrated under voltage release

Overload release current setting

320.0 .. 800A

Number of poles

3

Rated voltage

600 .. 600V

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Type of control element

Push button

Device construction

Built-in device fixed built-in technique

Motor drive integrated

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

With switched-off indicator

Integrated earth fault protection

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

Complete device with protection unit

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Number of auxiliary contacts as change-over contact

4