Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
With switched-off indicatorYes
Type of control elementPush button
Motor drive integratedNo
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitBack side
With integrated under voltage releaseNo
Adjustment range short-term delayed short-circuit release720 - 12000A
Overload release current setting480 - 1200A
Number of auxiliary contacts as normally open contact0
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release1800 - 18000A
Complete device with protection unitYes
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Integrated earth fault protectionYes
Rated permanent current Iu1200A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user