Technical specifications

Number of auxiliary contacts as normally open contact0
Overload release current setting100.0 - 250A
Type of electrical connection of main circuitBolt connection
Position of connection for main current circuitBack side
Number of auxiliary contacts as normally closed contact0
Motor drive optionalYes
With switched-off indicatorYes
Type of control elementPush button
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionNo
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Adjustment range short-term delayed short-circuit release- - -A
Suitable for DIN rail (top hat rail) mountingNo
With under voltage releaseNo
Motor drive integratedNo
Adjustment range undelayed short-circuit release375.0 - 3750A
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Rated permanent current Iu250A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077338R1 | E2.2V-A 250 Ekip Dip LI 3p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Overload release current setting

100.0 .. 250A

Type of electrical connection of main circuit

Bolt connection

Position of connection for main current circuit

Back side

Number of auxiliary contacts as normally closed contact

0

Motor drive optional

With switched-off indicator

Type of control element

Push button

Device construction

Built-in device fixed built-in technique

Integrated earth fault protection

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Adjustment range short-term delayed short-circuit release

- .. -A

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Motor drive integrated

Adjustment range undelayed short-circuit release

375.0 .. 3750A

DIN rail (top hat rail) mounting optional

Complete device with protection unit

Rated permanent current Iu

250A

Number of poles

3

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA