Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
With switched-off indicatorYes
With integrated under voltage releaseNo
Degree of protection (IP)IP30
Overload release current setting100 - 250A
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Type of control elementPush button
Adjustment range undelayed short-circuit release375 - 3750A
Number of auxiliary contacts as change-over contact4
Position of connection for main current circuitBack side
Adjustment range short-term delayed short-circuit release150 - 2500A
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Integrated earth fault protectionYes
Rated permanent current Iu250A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user