Degree of protection (IP)IP30
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitBolt connection
Type of control elementPush button
Position of connection for main current circuitBack side
Motor drive integratedNo
Number of auxiliary contacts as change-over contact4
Overload release current setting320.0 - 800A
With integrated under voltage releaseNo
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionYes
Complete device with protection unitYes
Device constructionBuilt-in device fixed built-in technique
Adjustment range undelayed short-circuit release1200.0 - 12000A
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu800 A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077367R1 | E2.2V-A 800 Ekip G Hi-Touch LSIG 3p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)

IP30

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Type of electrical connection of main circuit

Bolt connection

Type of control element

Push button

Position of connection for main current circuit

Back side

Motor drive integrated

Number of auxiliary contacts as change-over contact

4

Overload release current setting

320.0 .. 800A

With integrated under voltage release

With switched-off indicator

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Complete device with protection unit

Device construction

Built-in device fixed built-in technique

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Motor drive optional

DIN rail (top hat rail) mounting optional

Rated permanent current Iu

800 A

Number of poles

3

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA