Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)IP30
Number of auxiliary contacts as normally closed contact0
Motor drive integratedNo
Type of control elementPush button
Position of connection for main current circuitBack side
Overload release current setting640.0 - 1600A
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Adjustment range short-term delayed short-circuit release960.0 - 16000A
With switched-off indicatorYes
With under voltage releaseNo
Motor drive optionalYes
Complete device with protection unitYes
Integrated earth fault protectionYes
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release2400.0 - 24000A
Device constructionBuilt-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mountingNo
Rated permanent current Iu1600A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077406R1 | E2.2B-A 1600 Ekip Hi-Touch LSIG 4p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)

IP30

Number of auxiliary contacts as normally closed contact

0

Motor drive integrated

Type of control element

Push button

Position of connection for main current circuit

Back side

Overload release current setting

640.0 .. 1600A

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

With switched-off indicator

With under voltage release

Motor drive optional

Complete device with protection unit

Integrated earth fault protection

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

Rated permanent current Iu

1600A

Number of poles

4

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.