Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting320 - 800A
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitBack side
With integrated under voltage releaseNo
Motor drive integratedNo
With switched-off indicatorYes
Type of control elementPush button
Device constructionBuilt-in device fixed built-in technique
Motor drive optionalYes
Adjustment range short-term delayed short-circuit release480 - 8000A
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release1200 - 12000A
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Complete device with protection unitYes
Rated permanent current Iu800A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user