Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Rated permanent current Iu2000A
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Number of poles4
Type of control elementPush button
Position of connection for main current circuitBack side
With switched-off indicatorYes
Motor drive integratedNo
Adjustment range short-term delayed short-circuit release1200.0 - 20000A
Rated voltage600 - 600V
Number of auxiliary contacts as normally closed contact0
Overload release current setting800.0 - 2000A
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release3000.0 - 30000A
With integrated under voltage releaseNo
Type of electrical connection of main circuitBolt connection
Integrated earth fault protectionNo
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077445R1 | E2.2H-A 2000 Ekip Hi-Touch LSI 4p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

2000A

Degree of protection (IP)

IP30

Number of auxiliary contacts as change-over contact

4

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Number of poles

4

Type of control element

Push button

Position of connection for main current circuit

Back side

With switched-off indicator

Motor drive integrated

Adjustment range short-term delayed short-circuit release

1200.0 .. 20000A

Rated voltage

600 .. 600V

Number of auxiliary contacts as normally closed contact

0

Overload release current setting

800.0 .. 2000A

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

With integrated under voltage release

Type of electrical connection of main circuit

Bolt connection

Integrated earth fault protection

Motor drive optional

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.