Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Device constructionBuilt-in device fixed built-in technique
Number of auxiliary contacts as change-over contact4
Overload release current setting640 - 1600A
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitBolt connection
Adjustment range undelayed short-circuit release2400 - 24000A
Type of control elementPush button
Motor drive optionalYes
With integrated under voltage releaseNo
Position of connection for main current circuitBack side
Number of auxiliary contacts as normally closed contact0
With switched-off indicatorYes
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release- - -A
Degree of protection (IP)IP30
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu1600A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user