Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Overload release current setting800 - 2000A
Position of connection for main current circuitBack side
Degree of protection (IP)IP30
Type of control elementPush button
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release3000 - 30000A
Number of auxiliary contacts as change-over contact4
Device constructionBuilt-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release- - -A
With under voltage releaseNo
With switched-off indicatorYes
Motor drive optionalYes
Number of auxiliary contacts as normally closed contact0
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu2000A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user