Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as change-over contact4
Overload release current setting800 - 2000A
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Type of electrical connection of main circuitBolt connection
Device constructionBuilt-in device fixed built-in technique
Position of connection for main current circuitBack side
Adjustment range undelayed short-circuit release3000 - 30000A
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release1200 - 20000A
Type of control elementPush button
Integrated earth fault protectionNo
Motor drive integratedNo
Motor drive optionalYes
Degree of protection (IP)IP30
Complete device with protection unitYes
Rated permanent current Iu2000A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA