Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Number of poles4
Number of auxiliary contacts as normally open contact0
Overload release current setting480.0 - 1200A
Rated permanent current Iu1200A
Type of control elementPush button
Motor drive optionalYes
With switched-off indicatorYes
Motor drive integratedNo
Position of connection for main current circuitBack side
Rated voltage600 - 600V
Type of electrical connection of main circuitBolt connection
Integrated earth fault protectionYes
Device constructionBuilt-in device fixed built-in technique
Degree of protection (IP)IP30
DIN rail (top hat rail) mounting optionalNo
Adjustment range short-term delayed short-circuit release720.0 - 12000A
Suitable for DIN rail (top hat rail) mountingNo
With under voltage releaseNo
Adjustment range undelayed short-circuit release1800.0 - 18000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077480R1 | E2.2S-A 1200 Ekip Dip LSIG 4p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Number of poles

4

Number of auxiliary contacts as normally open contact

0

Overload release current setting

480.0 .. 1200A

Rated permanent current Iu

1200A

Type of control element

Push button

Motor drive optional

With switched-off indicator

Motor drive integrated

Position of connection for main current circuit

Back side

Rated voltage

600 .. 600V

Type of electrical connection of main circuit

Bolt connection

Integrated earth fault protection

Device construction

Built-in device fixed built-in technique

Degree of protection (IP)

IP30

DIN rail (top hat rail) mounting optional

Adjustment range short-term delayed short-circuit release

720.0 .. 12000A

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Adjustment range undelayed short-circuit release

1800.0 .. 18000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.