Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Device constructionBuilt-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact0
Type of control elementPush button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Motor drive optionalYes
Adjustment range undelayed short-circuit release2400.0 - 24000A
Rated voltage600 - 600V
Suitable for DIN rail (top hat rail) mountingNo
Rated permanent current Iu1600A
Degree of protection (IP)IP30
Adjustment range short-term delayed short-circuit release960.0 - 16000A
Position of connection for main current circuitBack side
Integrated earth fault protectionYes
Number of poles4
With under voltage releaseNo
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as normally open contact0
Overload release current setting640.0 - 1600A
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077490R1 | E2.2S-A 1600 Ekip Dip LSIG 4p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally closed contact

0

Type of control element

Push button

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Motor drive optional

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Rated voltage

600 .. 600V

Suitable for DIN rail (top hat rail) mounting

Rated permanent current Iu

1600A

Degree of protection (IP)

IP30

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

Position of connection for main current circuit

Back side

Integrated earth fault protection

Number of poles

4

With under voltage release

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as normally open contact

0

Overload release current setting

640.0 .. 1600A

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

DIN rail (top hat rail) mounting optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.