Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu400 A
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
Number of poles4
Overload release current setting160.0 - 400A
With integrated under voltage releaseNo
Rated voltage600 - 600V
Type of control elementPush button
Degree of protection (IP)IP30
Position of connection for main current circuitBack side
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release240.0 - 4000A
Motor drive optionalYes
Integrated earth fault protectionYes
Adjustment range undelayed short-circuit release600.0 - 6000A
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077527R1 | E2.2V-A 400 Ekip G Hi-Touch LSIG 4p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

400 A

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally open contact

0

Number of poles

4

Overload release current setting

160.0 .. 400A

With integrated under voltage release

Rated voltage

600 .. 600V

Type of control element

Push button

Degree of protection (IP)

IP30

Position of connection for main current circuit

Back side

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

With switched-off indicator

Adjustment range short-term delayed short-circuit release

240.0 .. 4000A

Motor drive optional

Integrated earth fault protection

Adjustment range undelayed short-circuit release

600.0 .. 6000A

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.