Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Motor drive integratedNo
Overload release current setting640.0 - 1600A
Type of electrical connection of main circuitConnection at separate chassis part
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
Type of control elementPush button
Adjustment range short-term delayed short-circuit release960.0 - 16000A
With under voltage releaseNo
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release2400.0 - 24000A
Integrated earth fault protectionYes
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated permanent current Iu1600A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077576R1 | E2.2B-A 1600 Ekip Hi-Touch LSIG 3p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Motor drive integrated

Overload release current setting

640.0 .. 1600A

Type of electrical connection of main circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Type of control element

Push button

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

With under voltage release

Suitable for DIN rail (top hat rail) mounting

Motor drive optional

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Integrated earth fault protection

Complete device with protection unit

Device construction

Built-in device slide-in technique (withdrawable)

Rated permanent current Iu

1600A

Number of poles

3

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.