Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Overload release current setting320.0 - 800A
Number of auxiliary contacts as change-over contact4
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Type of electrical connection of main circuitConnection at separate chassis part
Type of control elementPush button
With under voltage releaseNo
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
Adjustment range undelayed short-circuit release1200.0 - 12000A
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Integrated earth fault protectionYes
Device constructionBuilt-in device slide-in technique (withdrawable)
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Motor drive integratedNo
Rated permanent current Iu800A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077580R1 | E2.2H-A 800 Ekip Dip LSIG 3p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Overload release current setting

320.0 .. 800A

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Type of electrical connection of main circuit

Connection at separate chassis part

Type of control element

Push button

With under voltage release

Suitable for DIN rail (top hat rail) mounting

Motor drive optional

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

DIN rail (top hat rail) mounting optional

Complete device with protection unit

Integrated earth fault protection

Device construction

Built-in device slide-in technique (withdrawable)

With switched-off indicator

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Motor drive integrated

Rated permanent current Iu

800A

Number of poles

3

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.