With integrated under voltage releaseNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Rated permanent current Iu1600A
Number of poles3
Number of auxiliary contacts as change-over contact4
Overload release current setting640.0 - 1600A
Degree of protection (IP)IP30
Rated voltage600 - 600V
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release960.0 - 16000A
With switched-off indicatorYes
Adjustment range undelayed short-circuit release2400.0 - 24000A
Motor drive optionalYes
Type of control elementPush button
Type of electrical connection of main circuitConnection at separate chassis part
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077605R1 | E2.2H-A 1600 Ekip Hi-Touch LSI 3p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

1600A

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Overload release current setting

640.0 .. 1600A

Degree of protection (IP)

IP30

Rated voltage

600 .. 600V

Position of connection for main current circuit

Connection at separate chassis part

Motor drive integrated

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

With switched-off indicator

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Motor drive optional

Type of control element

Push button

Type of electrical connection of main circuit

Connection at separate chassis part

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Device construction

Built-in device slide-in technique (withdrawable)

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Complete device with protection unit