Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles3
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Rated permanent current Iu1600A
Rated voltage600 - 600V
Overload release current setting640.0 - 1600A
With integrated under voltage releaseNo
Type of electrical connection of main circuitConnection at separate chassis part
Motor drive integratedNo
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Type of control elementPush button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Adjustment range undelayed short-circuit release2400.0 - 24000A
Integrated earth fault protectionYes
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release960.0 - 16000A
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077667R1 | E2.2S-A 1600 Ekip G Hi-Touch LSIG 3p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

1600A

Rated voltage

600 .. 600V

Overload release current setting

640.0 .. 1600A

With integrated under voltage release

Type of electrical connection of main circuit

Connection at separate chassis part

Motor drive integrated

Position of connection for main current circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Type of control element

Push button

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Integrated earth fault protection

With switched-off indicator

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

DIN rail (top hat rail) mounting optional

Motor drive optional

Complete device with protection unit

Device construction

Built-in device slide-in technique (withdrawable)

Suitable for DIN rail (top hat rail) mounting

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.