Technical specifications
1SDA077674R1 | E2.2S-A 2000 Ekip G Touch LSIG 3p WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Type of control element
Push button
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
Overload release current setting
800.0 .. 2000A
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Motor drive optional
With under voltage release
Complete device with protection unit
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
Rated permanent current Iu
2000A
Number of poles
3
Rated voltage
600 .. 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA