Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu2000A
Number of auxiliary contacts as change-over contact4
Number of poles3
Overload release current setting800.0 - 2000A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Rated voltage600 - 600V
Motor drive integratedNo
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
Type of electrical connection of main circuitConnection at separate chassis part
Integrated earth fault protectionYes
Motor drive optionalYes
Adjustment range undelayed short-circuit release3000.0 - 30000A
Adjustment range short-term delayed short-circuit release1200.0 - 20000A
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Type of control elementPush button
Suitable for DIN rail (top hat rail) mountingNo
Complete device with protection unitYes
With under voltage releaseNo
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077676R1 | E2.2S-A 2000 Ekip Hi-Touch LSIG 3p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

2000A

Number of auxiliary contacts as change-over contact

4

Number of poles

3

Overload release current setting

800.0 .. 2000A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated voltage

600 .. 600V

Motor drive integrated

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Type of electrical connection of main circuit

Connection at separate chassis part

Integrated earth fault protection

Motor drive optional

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

Adjustment range short-term delayed short-circuit release

1200.0 .. 20000A

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Type of control element

Push button

Suitable for DIN rail (top hat rail) mounting

Complete device with protection unit

With under voltage release

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.