Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA077713R1 | E2.2V-A 1200 Ekip Touch LSIG 3p WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Rated voltage
600 .. 600V
With integrated under voltage release
Number of auxiliary contacts as change-over contact
4
Overload release current setting
480.0 .. 1200A
Number of poles
3
Type of electrical connection of main circuit
Connection at separate chassis part
Rated permanent current Iu
1200A
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
With switched-off indicator
Adjustment range short-term delayed short-circuit release
720.0 .. 12000A
Adjustment range undelayed short-circuit release
1800.0 .. 18000A
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive optional
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Complete device with protection unit