Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitConnection at separate chassis part
Number of auxiliary contacts as change-over contact4
Overload release current setting640 - 1600A
Type of control elementPush button
Degree of protection (IP)IP30
Motor drive integratedNo
Type of electrical connection of main circuitConnection at separate chassis part
With switched-off indicatorYes
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release2400 - 24000A
Motor drive optionalYes
With under voltage releaseNo
Adjustment range short-term delayed short-circuit release- - -A
Rated permanent current Iu1600A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user