Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Number of auxiliary contacts as normally open contact0
Overload release current setting800 - 2000A
Type of electrical connection of main circuitConnection at separate chassis part
Type of control elementPush button
With integrated under voltage releaseNo
With switched-off indicatorYes
Degree of protection (IP)IP30
Adjustment range short-term delayed short-circuit release1200 - 20000A
Adjustment range undelayed short-circuit release3000 - 30000A
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Complete device with protection unitYes
Motor drive optionalYes
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu2000A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA