Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA077733R1 | E2.2V-A 2000 Ekip Touch LSIG 3p WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Overload release current setting
800.0 .. 2000A
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Type of control element
Push button
Motor drive integrated
With integrated under voltage release
Motor drive optional
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
With switched-off indicator
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Connection at separate chassis part
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
2000A
Number of poles
3
Rated voltage
600 .. 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA