Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting800 - 2000A
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitConnection at separate chassis part
With integrated under voltage releaseNo
Adjustment range undelayed short-circuit release3000 - 30000A
Type of control elementPush button
With switched-off indicatorYes
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range short-term delayed short-circuit release1200 - 20000A
Integrated earth fault protectionNo
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated permanent current Iu2000A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user