Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as change-over contact4
Adjustment range short-term delayed short-circuit release960.0 - 16000A
Type of electrical connection of main circuitConnection at separate chassis part
Rated permanent current Iu1600A
Overload release current setting640.0 - 1600A
Number of auxiliary contacts as normally open contact0
Type of control elementPush button
Motor drive integratedNo
With switched-off indicatorYes
Rated voltage600 - 600V
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Motor drive optionalYes
Adjustment range undelayed short-circuit release2400.0 - 24000A
With integrated under voltage releaseNo
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Number of poles4
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077789R1 | E2.2N-A 1600 Ekip Dip LSI 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as change-over contact

4

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

Type of electrical connection of main circuit

Connection at separate chassis part

Rated permanent current Iu

1600A

Overload release current setting

640.0 .. 1600A

Number of auxiliary contacts as normally open contact

0

Type of control element

Push button

Motor drive integrated

With switched-off indicator

Rated voltage

600 .. 600V

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Number of auxiliary contacts as normally closed contact

0

DIN rail (top hat rail) mounting optional

Device construction

Built-in device slide-in technique (withdrawable)

Motor drive optional

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

With integrated under voltage release

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Number of poles

4

Complete device with protection unit