Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of poles4
Rated permanent current Iu800A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Rated voltage600 - 600V
Position of connection for main current circuitConnection at separate chassis part
Overload release current setting320.0 - 800A
With switched-off indicatorYes
Integrated earth fault protectionNo
Motor drive integratedNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Type of control elementPush button
Type of electrical connection of main circuitConnection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release1200.0 - 12000A
With under voltage releaseNo
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077812R1 | E2.2S-A 800 Ekip Touch LSI 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of poles

4

Rated permanent current Iu

800A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Rated voltage

600 .. 600V

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

320.0 .. 800A

With switched-off indicator

Integrated earth fault protection

Motor drive integrated

Device construction

Built-in device slide-in technique (withdrawable)

Type of control element

Push button

Type of electrical connection of main circuit

Connection at separate chassis part

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

With under voltage release

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Motor drive optional

DIN rail (top hat rail) mounting optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.