Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA077813R1 | E2.2S-A 800 Ekip Touch LSIG 4p WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
320.0 .. 800A
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally closed contact
0
With integrated under voltage release
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Connection at separate chassis part
Type of control element
Push button
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
With switched-off indicator
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Motor drive integrated
Motor drive optional
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Complete device with protection unit
Rated permanent current Iu
800 A
Number of poles
4
Rated voltage
600 .. 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA